RS/M 70-190
Modulating • 512 - 8,673 MBTUH



RS/M Model 70 100 130 190
Capacity (MBTUH)(1) 512 - 3,084 570 - 4,405 607 - 5,545 1,781 - 8,673
Combustion Air Motor Voltage (2)(3) 230-460-575/3/60 230-460-575/3/60 230-460-575/3/60 230-460-575/3/60
HP 11/2 21/2 3 51/2
Amperage Draw 4.8 / 2.8 / 2.3 6.7 / 3.9 / 3.2 8.8 / 5.1 / 4.1 15.8 / 9.1 / 7.3
Sound Levels dBA 75.0 77.0 78.5 83.1
Max. Chamber Pressure ("w.c.) @ high fire 2.0 2.8 1.6 0.8
Min. Gas Pressure ("w.c.)(4)(5) 7.0 7.0 8.0 7.0
(1) Ratings based on 1,000 Btu/ft.3 and .64 specific gravity.
(2) Other voltages available on request.
(3) A separate 120/1/60 control voltage supply is required.
(4) Based on natural gas.
(5) Honeywell, Dungs and Siemens gas trains available.