| Model |
On-Off |
2-Stage |
| G120
|
G200
|
G400
|
G750
|
G900
|
| Fuel
Type |
Natural |
Propane |
Natural |
Propane |
Natural |
Propane |
Natural |
Propane |
Natural |
Propane |
Firing
Rate
Btuh x 1,000 |
38
- 120 |
70
- 200 |
170
- 400 |
250
- 750 |
250-4901
360-9002 |
Manifold
Gas Pressure
("w.c.)
min.-max. |
.52-2.05 |
.51-1.87 |
.7-1.84 |
.9-2.96 |
.9-1.8 |
1.04-
3.04 |
1.4-2.1 |
1.0-3.0 |
.55-1.11
2.3-3.32 |
1.7-3.41 2.6-6.02 |
Burner
Supply Pressure
( "w.c.)
min.-max. |
4
- 10 |
8
- 13 |
4
- 10 |
8
- 13 |
4
- 10 |
8
- 13 |
7
- 14 |
8
- 13 |
7
- 14 |
8
- 13 |
| Motor
Ratings |
120v
60Hz 2.2amp 3250rpm |
120v
60Hz 4.3amp 3250rpm |
| (1)
Low Fire (2) High Fire |
40-Series gas
burners are CSA, CGA and AGA approved.  |
|