RLS 70 - 130
Modulating Gas • 854 - 5,292 MBTUH
2-Stage Oil • 6.1 - 37.8 GPH



RLS Model 70 100 130
Capacity (MBTUH)(1) 854 - 3,094 1,330 - 4,396 1,750 - 5,292
Capacity (GPH)(2) 6.1 - 22.1 9.5 - 31.4 12.5 - 37.8
Combustion
Air Motor
Voltage(3)(4) 230 - 460 - 575/3/60 230 - 460 - 575/3/60 230 - 460 - 575/3/60
HP 11/2 21/2 3
Amperage Draw 4.8 / 2.8 / 2.3 6.7 / 3.9 / 3.2 8.8 / 5.1 / 4.1
Sound Levels dBA 74.0 77.5 80.0
Max. Chamber Pressure ("w.c.) @ high fire 2.0 2.6 1.6
Min. Gas Pressure ("w.c.)(5)(6) 7.0 7.0 8.0
(1) Ratings based on 1,000 Btu/ft.3 and .64 specific gravity.
(2) Ratings based on 140,000 Btu/Gallon for No.2 fuel oil.
(3) Other Voltage available on request.
(4) A separate 120/1/60 control voltage supply is required.
(5) Based on natural gas.
(6) Honeywell, Dungs and Siemens gas trains available.